13)Facility emergency exit doors:工厂紧急出口门
Do not have a landing with at least 1 meter (3 feet) before beginning of first step.没有距离第一个阶梯1米(3英尺)的楼梯平台(缓冲带)
14)Facility emergency fire alarms:工厂紧急火灾警报器
Have error indicators on the fire alarm control panel.消防警报器控制板上错误的指导
15)Facility emergency fire alarms:警铃
Are not audible;听不到警铃
Do not have beacon or flashing lights in high-noise areas.噪音大的区域未安装信号灯和闪光式警铃
16)Facility emergency fire alarms:警铃
Are not connected to a secondary power source.未连接备用电源
17)Emergency exit lights:应急灯
Are not connected to a secondary power source.未连接备用电源
18)Facility emergency exit doors:紧急出口门
Are not side-hinged doors;不是侧铰链门
Do not open in the direction of travel with a single motion;不能一个动作向逃生方向开启
Do not close automatically when leading to a staircase;当推开至楼梯时不能自动关闭
19)Emergency assembly areas:工厂紧急集合区域
Are not designated on evacuation plan;未在疏散计划图上有指明
Are not located along each fire escape route.并非每个逃生路径均可前往
20)Fire extinguishers:灭火器
Are not present on every floor of the facility;不能覆盖工厂的每一层
Are not present in every production area;不能覆盖工厂每个区域
Are not present in areas where there is storage of materials labeled as flammable. 不能覆盖储存易燃物品的区域
21)Fire Extinguishers:灭火器
Are not mounted;未离地放置
Are mounted above 1.5 meters (5 feet) from ground to top of fire extinguisher.灭火器顶部距离大于1.5米
22)Fire Extinguishers:灭火器
Are overcharged;压力过大
Are undercharged.压力不足
23)Materials labeled as hazardous, combustible, or flammable:危险物品、可燃或易燃物品
Are not stored in containers labeled as anti-static;未存放在标识了防静电的容器内
Are not grounded.未接地
24)Electrical wiring:电线
Is damaged or exposed; 是损坏的或者暴露的
Is connected through extension cords通过延长线连接