13Facility emergency exit doors:工厂紧急出口门

  • Do not have a landing with at least 1 meter (3 feet) before beginning of first step.没有距离第一个阶梯1米(3英尺)的楼梯平台(缓冲带)

 

14Facility emergency fire alarms:工厂紧急火灾警报器

  • Have error indicators on the fire alarm control panel.消防警报器控制板上错误的指导

 

15Facility emergency fire alarms:警铃

  • Are not audible;听不到警铃

  • Do not have beacon or flashing lights in high-noise areas.噪音大的区域未安装信号灯和闪光式警铃

 

16Facility emergency fire alarms:警铃

  • Are not connected to a secondary power source.未连接备用电源

 

17Emergency exit lights:应急灯

  • Are not connected to a secondary power source.未连接备用电源

 

18Facility emergency exit doors:紧急出口门

  • Are not side-hinged doors;不是侧铰链门

  • Do not open in the direction of travel with a single motion;不能一个动作向逃生方向开启

  • Do not close automatically when leading to a staircase;当推开至楼梯时不能自动关闭

 

19Emergency assembly areas:工厂紧急集合区域

  • Are not designated on evacuation plan;未在疏散计划图上有指明

  • Are not located along each fire escape route.并非每个逃生路径均可前往

 

20Fire extinguishers:灭火器

  • Are not present on every floor of the facility;不能覆盖工厂的每一层

  • Are not present in every production area;不能覆盖工厂每个区域

  • Are not present in areas where there is storage of materials labeled as flammable. 不能覆盖储存易燃物品的区域

 

21Fire Extinguishers:灭火器

  • Are not mounted;未离地放置

  • Are mounted above 1.5 meters (5 feet) from ground to top of fire extinguisher.灭火器顶部距离大于1.5

 

22Fire Extinguishers:灭火器

  • Are overcharged;压力过大

  • Are undercharged.压力不足

 

23Materials labeled as hazardous, combustible, or flammable:危险物品、可燃或易燃物品

  • Are not stored in containers labeled as anti-static;未存放在标识了防静电的容器内

  • Are not grounded.未接地

 

24Electrical wiring:电线

  • Is damaged or exposed; 是损坏的或者暴露的

  • Is connected through extension cords通过延长线连接

 